Vapour Pressure of Water Calculator

Calculate the saturation vapour pressure of water at any temperature using the Buck, Magnus, Tetens, and Goff-Gratch equations. Includes dew point, humidity, and psychrometric conversions.

Saturation VP (Buck)
23.383 hPa
2.3383 kPa
Saturation VP (Magnus)
23.382 hPa
Magnus-Tetens equation
VP in mmHg
17.539
0.023078 atm
Actual VP
14.030 hPa
At 60% RH
Dew Point
12.0 °C
Dew depression: 8.0 °C
Humidity Ratio
8.73 g/kg
Abs humidity: 10.37 g/m³

Equation Comparison

Buck (1981)
23.383 hPa
Magnus-Tetens
23.382 hPa
Tetens (1930)
23.381 hPa

Dew Point Comfort Scale

Dry (<10°)
Comfort (<16°)
Humid (<20°)
Oppressive (<26°)
Dangerous (<30°)
12.0°

Steam Table (−40 °C to 100 °C)

Planning notes, formulas, and examples

About the Vapour Pressure of Water Calculator

The vapour pressure of water is the equilibrium partial pressure of water vapour above a flat surface of liquid water at a given temperature. It is one of the most frequently needed physical properties in meteorology, HVAC engineering, chemical processing, food science, and environmental monitoring.

Several empirical equations approximate this relationship with different levels of accuracy. The Buck equation (1981) is accurate to within 0.05% from −80 °C to 50 °C. The Magnus-Tetens equation is simpler and widely used in meteorology. The Goff-Gratch equation, adopted by the WMO, offers the highest accuracy across the full range from −100 °C to +100 °C. For engineering applications, the Antoine equation parameterized for water is also common.

This calculator computes saturation vapour pressure using all four equations for comparison, derives dew point from relative humidity, and provides a comprehensive steam table reference from −40 °C to 100 °C.

When This Page Helps

Accurate water vapour pressure data is critical for weather forecasting, humidity control in data centers, greenhouses, and cleanrooms, drying process design, HVAC load calculations, and food preservation science. A reliable conversion-ready value also helps when reconciling readings from mixed unit systems used in laboratory reports, instrumentation panels, and international technical references.

How to Use the Inputs

  1. Enter the temperature in °C (or select from common presets).
  2. View the saturation vapour pressure calculated by four different equations.
  3. Optionally enter relative humidity to calculate the actual vapour pressure and dew point.
  4. Enter actual vapour pressure to calculate relative humidity and dew point.
  5. Compare results across equations and review the steam table reference.
  6. Use the psychrometric section for wet-bulb/dry-bulb conversions.
  7. Check the meteorological applications table for common humidity scenarios.
Formula used
Buck (1981): e_s = 6.1121 × exp((18.678 − T/234.5) × T / (257.14 + T)) hPa, where T is in °C. Magnus: e_s = 6.1078 × exp(17.27 × T / (T + 237.3)) hPa. Dew point from RH: T_d ≈ (237.3 × ln(e_a / 6.1078)) / (17.27 − ln(e_a / 6.1078)).

Example Calculation

Result: e_s = 23.39 hPa, e_a = 14.03 hPa, T_d = 12.0 °C

At 20 °C the saturation vapour pressure is 23.39 hPa. At 60% RH the actual vapour pressure is 14.03 hPa, and the dew point is 12.0 °C.

Tips & Best Practices

  • For sub-zero temperatures, use the saturation pressure over ice, not liquid water.
  • Most weather stations report pressure in hPa (= mbar). 1 kPa = 10 hPa.
  • A dew point spread < 3 °C means fog or low clouds are likely.
  • ASHRAE standard psychrometric charts are based on the Hyland-Wexler equations, very close to Buck.
  • Hair hygrometers and capacitive RH sensors are calibrated against these equations.
  • The August-Roche-Magnus equation is the simplified form most often cited in textbooks.

Comparison of Vapour Pressure Equations

The four most common equations for the saturation vapour pressure of water are:

1. **Buck (1981)** — Best overall accuracy for meteorological applications (±0.05% from −80 to +50 °C). 2. **Magnus-Tetens** — Simple, widely taught, adequate for most purposes (±0.4% from −40 to +50 °C). 3. **Tetens (1930)** — Original formulation, slightly less accurate than modified Magnus. 4. **Goff-Gratch (1946)** — WMO reference standard, most complex but highest accuracy.

For temperatures above 100 °C, steam tables from IAPWS-IF97 should be used instead.

Psychrometric Applications

HVAC engineers use the vapour pressure of water in psychrometric calculations that relate dry-bulb temperature, wet-bulb temperature, dew point, relative humidity, humidity ratio, enthalpy, and specific volume. The psychrometric chart is a graphical tool that encodes these relationships.

Health and Comfort

Human comfort depends on both temperature and humidity. The dew point is a better indicator of mugginess than relative humidity: dew points below 10 °C feel dry, 10-16 °C comfortable, 16-20 °C humid, and above 20 °C oppressive. Heat index calculations rely on accurate vapour pressure data.

Sources & Methodology

Last updated:

Frequently Asked Questions

  • Vapour pressure is the equilibrium pressure of the vapour above its liquid. Partial pressure is the actual pressure contributed by water vapour in the atmosphere. RH = (partial pressure / saturation pressure) × 100%.