Amp to Wire Size Calculator

Convert amperage to wire gauge using NEC ampacity tables. Copper and aluminum, temperature ratings, conduit fill, and ambient temperature derating.

Select the correct wire gauge from amperage using NEC ampacity tables with temperature and conduit fill derating.

A
°C
Recommended Wire
10 AWG
copper at 75°C
Base Ampacity
35.00 A
Before derating
Derated Ampacity
35.00 A
×1 conduit ×1 temp
Safety Margin
16.67%
35.00 A available vs 30 A needed
Conduit Derating
100%
1-3 conductors
Temp Derating
100%
30°C ambient
Ampacity Margin
30.00 / 35.00 A

NEC Ampacity Table — Copper

AWGmm²Base AmpsDeratedStatus
142.0820.00 A20.00 A
123.3125.00 A25.00 A
105.2635.00 A35.00 A✓ (16.67%)
88.3750.00 A50.00 A✓ (66.67%)
613.365.00 A65.00 A✓ (116.67%)
421.285.00 A85.00 A✓ (183.33%)
326.7100.00 A100.00 A✓ (233.33%)
233.6115.00 A115.00 A✓ (283.33%)
142.4130.00 A130.00 A✓ (333.33%)
1/053.5150.00 A150.00 A✓ (400.00%)
2/067.4175.00 A175.00 A✓ (483.33%)
3/085200.00 A200.00 A✓ (566.67%)
4/0107230.00 A230.00 A✓ (666.67%)
Planning notes, formulas, and examples

About the Amp to Wire Size Calculator

Selecting wire gauge based on amperage is the most fundamental task in electrical wiring. The National Electrical Code (NEC) Table 310.16 specifies the maximum current each wire size can safely carry, depending on conductor material, insulation temperature rating, and installation conditions.

However, simply looking up the base ampacity is not enough. The NEC requires derating when multiple conductors share a conduit (reducing heat dissipation) or when ambient temperature exceeds the standard 30°C. These derating factors can reduce the effective ampacity by 20-50%, often bumping you up to the next wire size.

This calculator applies NEC ampacity tables with both conduit fill and temperature derating, showing the minimum wire gauge that safely carries your required current. It displays a complete table so you can evaluate options and understand the margin at each gauge. In practice, the final choice should still be checked against the actual installation, because conductor count, ambient heat, and terminal ratings can change the required gauge quickly.

When This Page Helps

Looking up NEC tables and applying derating factors is a multi-step process that is easy to get wrong. Forgetting conduit derating or ambient temperature correction can result in an undersized conductor — a code violation and safety hazard.

This calculator automates the entire process: select your conditions and see the minimum compliant wire gauge with full derating applied. The comparison table shows every gauge and its derated ampacity, so you can also evaluate the cost/benefit of upsizing for future capacity.

How to Use the Inputs

  1. Enter the required circuit amperage.
  2. Select the insulation temperature rating (60°C, 75°C, or 90°C).
  3. Choose copper or aluminum conductor.
  4. Select the number of current-carrying conductors in the conduit.
  5. Enter the ambient temperature if above 30°C.
  6. Review the recommended gauge with full derating applied.
Formula used
Derated Ampacity = Base Ampacity × Conduit Factor × Temperature Factor. Select the smallest wire whose derated ampacity ≥ required amps. Conduit factors: 1-3 conductors = 100%, 4-6 = 80%, 7-9 = 70%, 10+ = 50%.

Example Calculation

Result: 10 AWG copper

10 AWG copper at 75°C has 35A ampacity. With 3 conductors at 30°C, no derating applies. 35A > 30A with a 17% margin.

Tips & Best Practices

  • When in doubt, use the 75°C column — most terminations (breakers, outlets, switches) are rated for 75°C even if the wire is rated for 90°C.
  • For residential work, many inspectors prefer 12 AWG minimum regardless of load, providing extra capacity for future additions.
  • Count only current-carrying conductors for conduit derating. Equipment grounding conductors and neutrals with only unbalanced current do not count.
  • In hot attics or engine rooms, ambient temperature derating can be severe — always check conditions.
  • Remember that breaker size must match the wire ampacity, not just the load. A 30A breaker requires 10 AWG wire.

NEC Table 310.16 Explained

NEC Table 310.16 is the most-referenced table in electrical work. It lists the allowable ampacity of insulated conductors from 14 AWG to 2000 kcmil for copper and aluminum at three temperature ratings: 60°C, 75°C, and 90°C. These values assume no more than 3 current-carrying conductors in a raceway at an ambient temperature of 30°C.

When conditions differ from these assumptions, the NEC requires adjustment. Table 310.15(C)(1) provides derating factors for more than 3 conductors in a raceway, and Table 310.15(B)(1) provides correction factors for ambient temperatures above 30°C. Both factors are multiplicative with the base ampacity.

Practical Wire Selection

In practice, wire selection involves more than just ampacity. You must also consider voltage drop (especially for long runs), physical size (will it fit in the conduit and boxes), flexibility (stranded vs. solid), and the installation environment (wet, dry, underground, exposed to sunlight). Ampacity sets the minimum gauge, but these other factors may dictate a larger wire.

Copper vs. Aluminum

Aluminum conductors have about 78% of the ampacity of copper at the same gauge — roughly equivalent to copper two sizes smaller. Aluminum is lighter and cheaper, making it preferred for large feeders and service entrance cables. For branch circuits (15-20A), copper is standard because aluminum requires special connectors and is more susceptible to connection problems at small gauges.

Sources & Methodology

Last updated:

Frequently Asked Questions

  • 10 AWG copper at 75°C (35A ampacity). For aluminum, 8 AWG (40A). If you have more than 3 conductors in conduit or high ambient temperature, you may need to upsize.