kVA to Amperage Calculator

Convert kVA to amps for single-phase and three-phase systems. Includes power factor, wire sizing, breaker selection, and power triangle.

kVA
V
0.0 to 1.0 — typically 0.8 to 0.95
100% for ideal, lower for real loads
%
Full-Load Current
30.07 A
At 480 V 3-phase
Real Power (kW)
20.00 kW
kVA × power factor
Reactive Power
15.00 kVAR
kVA × sin(φ)
Breaker Size
40 A
125% of full-load current, rounded up
Wire Size
8 AWG (8.37 mm²)
NEC-based recommendation (75°C copper)
Power Factor Angle
36.9°
PF = 0.8

Power Triangle

20.0 kW15.0 kVAR25.0 kVAφ = 36.9°

Common System Voltages

kVA120V 1Φ208V 3Φ240V 1Φ480V 3Φ
541.713.920.86.0
1083.327.841.712.0
25208.369.4104.230.1
50416.7138.8208.360.1
75625.0208.2312.590.2
100833.3277.6416.7120.3
2001,666.7555.1833.3240.6
5004,166.71,387.92,083.3601.4

NEC Wire Ampacity Table (75°C Copper)

AWGAmpacity (A)Cross Section (mm²)
14152.08
12203.31
10305.26
8408.37
65513.3
47021.2
29533.6
1/012553.5
2/014567.4
3/016585
4/0195107
Planning notes, formulas, and examples

About the kVA to Amperage Calculator

Converting kVA (kilovolt-amperes) to amperes is one of the most common calculations in electrical engineering and power system design. Whether you are sizing a transformer, selecting circuit breakers, choosing wire gauges, or specifying generator capacity, you need to know the actual current draw in amperes to make safe and code-compliant decisions.

The relationship between kVA and amps depends on whether you have a single-phase or three-phase system. For single-phase circuits, the current equals the apparent power divided by the voltage. For three-phase systems, the voltage is multiplied by the square root of 3 (approximately 1.732), which accounts for the phase relationship between the three conductors.

This calculator handles both single-phase and three-phase conversions, incorporates power factor and efficiency for real-world accuracy, and provides practical guidance including NEC-compliant wire sizing and breaker recommendations. The power triangle visualization clearly shows the relationship between real power (kW), reactive power (kVAR), and apparent power (kVA).

When This Page Helps

Electrical equipment ratings are commonly given in kVA, but practical installation decisions — wire size, breaker rating, conduit fill, and panel capacity — all depend on the actual current in amperes. This calculator bridges that gap, converting apparent power to current while accounting for real-world factors like power factor and system efficiency.

The built-in wire sizing and breaker recommendations based on NEC standards help you move directly from a load calculation to a material specification, saving time and reducing the risk of undersizing critical electrical components.

How to Use the Inputs

  1. Enter the apparent power rating in kVA from your equipment nameplate or load calculation.
  2. Enter the system voltage (e.g., 120V, 208V, 240V, 480V).
  3. Select single-phase (1Φ) or three-phase (3Φ) configuration.
  4. Enter the power factor (typically 0.8 to 0.95 for most loads).
  5. Optionally adjust efficiency for real-world equipment losses.
  6. Read the full-load current, breaker size, and wire recommendation.
  7. Reference the comparison table for common system voltages.
Formula used
kVA to Amps Conversion: • Single Phase: I = (kVA × 1000) / V • Three Phase: I = (kVA × 1000) / (√3 × V) • Real Power: P (kW) = S (kVA) × PF • Reactive Power: Q (kVAR) = S × √(1 - PF²) • Breaker Size: ≥ 125% of full-load current Where I = current (A), V = voltage (V), S = apparent power (kVA), PF = power factor

Example Calculation

Result: 90.21 A full-load current, 120 A breaker, 1/0 AWG wire

For 75 kVA at 480V three-phase: I = 75000 / (1.732 × 480) = 90.21 A. At PF = 0.85, real power = 63.75 kW and reactive power = 39.53 kVAR. NEC requires 125% for continuous loads, so minimum breaker is 113 A → 120 A standard size.

Tips & Best Practices

  • Always size wires and breakers based on apparent power (kVA) not real power (kW) — current flows at the kVA level regardless of power factor.
  • Use 125% of full-load current for continuous loads per NEC Article 210.20.
  • For three-phase systems at 208V, note that 208V is NOT 240V — using the wrong voltage changes your amperage by 15%.
  • Consider voltage drop for long wire runs — upsize wire by one or two AWG for distances over 100 feet.
  • When sizing generators, use kVA rating directly — generators are limited by current capacity, not just real power output.
  • Factor in future load growth — size 120-150% of current requirements when possible.

Understanding Apparent Power (kVA)

Apparent power, measured in kVA, represents the total electrical power flowing through a circuit — both the real power that does useful work (kW) and the reactive power that sustains electromagnetic fields in motors and transformers (kVAR). These three quantities form the power triangle: S² = P² + Q², where S is apparent power, P is real power, and Q is reactive power.

Electrical equipment like transformers, generators, and UPS systems are rated in kVA because their windings and conductors must carry the full apparent current regardless of power factor. A 100 kVA transformer at 0.8 power factor delivers only 80 kW of useful power, but the conductors must still handle the full 100 kVA current.

Single-Phase vs Three-Phase Systems

Single-phase power uses two conductors (line and neutral) and delivers power as P = V × I × PF. Three-phase power uses three conductors with voltages 120° apart, delivering power as P = √3 × V × I × PF. This phase relationship means three-phase delivers 73% more power than single-phase using the same wire sizes and voltage.

In commercial and industrial settings, three-phase is standard for loads above 5 kW because it is more efficient, requires smaller conductors per unit of power, and produces smoother power delivery for motors. Residential services are typically single-phase (split-phase 240/120V).

Practical Installation Considerations

After calculating amperage, several NEC requirements affect your final design. Continuous loads (3+ hours) require 125% derating. Ambient temperature above 30°C requires ampacity correction factors. Conduit fill above three current-carrying conductors requires additional derating. Voltage drop should be limited to 3% for branch circuits and 5% for total (feeder plus branch).

Sources & Methodology

Last updated:

Frequently Asked Questions

  • kVA (kilovolt-amperes) is apparent power — the total power flowing in the circuit. kW (kilowatts) is real power — the portion that does useful work. They are related by the power factor: kW = kVA × PF. For resistive loads (PF = 1), they are equal.