Wire Size Calculator

Calculate the correct wire gauge (AWG) for any circuit. Factors in ampacity, voltage drop, NEC continuous load rule, conduit fill derating, and insulation rating. Includes NEC ampacity table and de...

A
V
%
Recommended AWG
AWG 8
8.37 mm² — voltage drop
Ampacity (AWG by)
AWG 12
Design current: 25.0 A
Voltage Drop (AWG by)
AWG 8
Min area: 5.75 mm²
Actual Voltage Drop
2.47 V (2.06%)
✓ Within limit
Power Loss
49.4 W
I²R in single-phase run
Wire Area
8.37 mm²
16,518 cmil

Gauge Comparison

AWG 4
85A
AWG 6
65A
AWG 8
← SELECTED
50A
AWG 10
35A
AWG 12
25A
AWG 14
20A

NEC Ampacity Table (Copper)

AWGmm²60°C75°C90°C
0000107.2195A230A260A
00085.0165A200A225A
0067.4145A175A195A
053.5125A150A170A
142.4110A130A150A
233.695A115A130A
326.785A100A115A
421.270A85A95A
613.355A65A75A
88.440A50A55A
105.330A35A40A
123.320A25A30A
142.115A20A25A
Derating Factors

Conductor Fill Derating (NEC 310.15)

ConductorsDerate Factor
4-6 conductors80%
7-9 conductors70%
10-20 conductors50%
21-30 conductors45%
31-40 conductors40%

Ambient Temperature Derating

Ambient60°C75°C90°C
31-35°C91%94%96%
36-40°C82%88%91%
41-45°C71%82%87%
46-50°C58%75%82%
51-55°C41%67%76%
Planning notes, formulas, and examples

About the Wire Size Calculator

Choosing the correct wire size is one of the most important decisions in electrical design. A wire that is too small can overheat, cause excessive voltage drop, or even start a fire. A wire that is too large wastes money unnecessarily. The National Electrical Code (NEC) provides ampacity tables and derating rules that form the foundation of wire sizing in North America.

Wire size selection must satisfy two independent criteria simultaneously: the wire must have enough ampacity to carry the current without overheating (NEC Article 310), and it must be large enough to keep the voltage drop within acceptable limits (NEC recommends 3% for branch circuits, 5% total including feeder). The stricter of the two requirements determines the final size.

This calculator handles both criteria: it checks the NEC ampacity tables (for 60°C, 75°C, and 90°C insulation ratings), applies the 125% continuous load rule, applies conduit fill derating factors, and simultaneously computes the minimum area needed for voltage drop compliance. It then recommends the larger of the two required sizes, showing which criterion was limiting.

When This Page Helps

Manual wire sizing requires cross-referencing NEC tables, applying multiple derating factors, and calculating voltage drop — a process prone to errors. This calculator automates the entire workflow: ampacity lookup, continuous load adjustment, conduit fill derating, and voltage drop calculation. It shows both the ampacity-required and voltage-drop-required gauges so you can verify which criterion controls.

How to Use the Inputs

  1. Enter the load current in amps and the system voltage.
  2. Select single-phase or three-phase, and set the maximum voltage drop percentage (typically 3%).
  3. Enter the one-way wire length (the calculator handles round-trip automatically).
  4. Select copper or aluminum conductor and insulation temperature rating.
  5. Set whether the load is continuous (NEC 125% rule) and enter the number of conductors in conduit.
  6. Read the recommended AWG gauge, which criterion limited the choice, and the actual voltage drop.
  7. Check the gauge comparison visual and NEC ampacity table for adjacent sizes.
Formula used
Ampacity sizing: I_design = I_load × 1.25 (if continuous) I_required = I_design / conduit_derate_factor Select smallest AWG with table ampacity ≥ I_required Voltage drop sizing: A_min = ρ × k × L × I / V_drop_max k = 2 (single-phase) or √3 (three-phase) V_drop_max = V_system × max_drop_pct / 100 Final size = larger of ampacity AWG and drop AWG

Example Calculation

Result: AWG 10 (limited by voltage drop)

For 20 A continuous load: design current = 25 A. AWG 10 at 75°C has 35 A ampacity. Voltage drop check: AWG 12 (3.31 mm²) gives 3.13% drop, exceeding 3% limit. AWG 10 (5.26 mm²) gives 1.97% — safe. Final: AWG 10.

Tips & Best Practices

  • NEC Article 210.19(A): Branch circuit conductors must have ampacity ≥ 125% of the continuous load plus 100% of the non-continuous load.
  • The 3% voltage drop recommendation is a guideline, not a hard requirement in the NEC. However, exceeding it can cause equipment issues — motors start slowly, lights dim, and electronic devices may malfunction.
  • For conduit runs with many conductors, don't forget derating: 4-6 conductors = 80%, 7-9 = 70%, 10-20 = 50%. This can significantly upsize your wire.
  • Aluminum wire requires one AWG size larger than copper for equivalent ampacity. Use only AL/CU rated terminations.
  • Three-phase circuits have a √3 (1.732) factor advantage: lower voltage drop per amp than single-phase for the same wire.
  • For long runs (>100 ft / 30 m), voltage drop almost always controls the wire size, not ampacity.

NEC Wire Sizing Workflow

Professional wire sizing follows a structured process: (1) Determine the design current (apply continuous load factor), (2) apply ambient temperature derating if above 30°C, (3) apply conduit fill derating if more than 3 current-carrying conductors, (4) select the smallest AWG from the appropriate table column (60/75/90°C) that meets all derating conditions, (5) separately calculate minimum area for voltage drop, (6) use the larger of the two sizes, (7) verify the result against available conduit size. This calculator automates steps 1 through 6.

Common Circuit Sizes in Residential Wiring

Most North American homes use AWG 14 (15 A) or AWG 12 (20 A) for general branch circuits, AWG 10 (30 A) for dryers and water heaters, AWG 8 (40 A) or AWG 6 (50-60 A) for ranges, and AWG 4/0 or larger for 200 A service entrances. EV chargers typically use AWG 8 (40 A) or AWG 6 (50 A). HVAC condensers range from AWG 12 to AWG 8 depending on tonnage.

Metric Wire Sizes (IEC 60228)

Outside North America, wire sizes are specified in mm² cross-sectional area. Common sizes: 1.5 mm² (≈ AWG 16), 2.5 mm² (≈ AWG 13), 4 mm² (≈ AWG 11), 6 mm² (≈ AWG 9), 10 mm² (≈ AWG 7), 16 mm² (≈ AWG 5), 25 mm² (≈ AWG 3). IEC standards use different ampacity ratings based on installation method (buried, in trunking, in free air, etc.) rather than insulation temperature alone.

Sources & Methodology

Last updated:

Frequently Asked Questions

  • NEC defines continuous load as one expected to run 3+ hours. Sustained current generates more heat than intermittent current because equipment has no time to cool. The 125% rule ensures the wire, breaker, and connections stay within safe temperature limits during extended operation.