Apparent Power Calculator

Calculate apparent power (VA), real power (W), reactive power (VAR), and power factor for AC circuits. Size transformers and generators accurately.

Apparent Power (S)
4.80 kVA
Total power the source delivers
Real Power (P)
4.08 kW
Actual useful work performed
Reactive Power (Q)
2.53 kVAR
Energy oscillating in inductance/capacitance
Phase Angle
31.8°
High reactance
PF Correction to 0.95
1.19 kVAR needed
Est. cost: $30
Current Components
17.0A real
10.5A reactive

Power Triangle

Real P (W)
4.08k
Reactive Q (VAR)
2.53k
Apparent S (VA)
4.80k

Power Factor Improvement Analysis

Power FactorApparent (VA)Reactive (VAR)Current (A)% of Baseline
0.606,8005,44028.3167%
0.705,8294,16224.3143%
0.805,1003,06021.3125%
0.854,8002,52920.0118%
0.904,5331,97618.9111%
0.954,2951,34117.9105%
0.994,12158117.2101%
1.004,080017.0100%
Common Load Power Factors
Load TypeTypical PFType
Resistive Heater1.00Unity
Incandescent Lamp1.00Unity
LED with PFC0.90-0.99Lagging
Motor (full load)0.85-0.90Lagging
Motor (half load)0.70-0.80Lagging
Motor (no load)0.10-0.30Lagging
Arc Welder0.50-0.60Lagging
Computer PSU (PFC)0.95-0.99Lagging
Fluorescent Lamp0.50-0.90Lagging
Planning notes, formulas, and examples

About the Apparent Power Calculator

The Apparent Power Calculator computes the relationship between apparent power (VA), real power (W), reactive power (VAR), and power factor in AC electrical circuits. Understanding these relationships is essential for properly sizing transformers, generators, UPS systems, and electrical distribution equipment.

In AC circuits, the power consumed by a load isn't simply voltage times current. Inductive and capacitive loads cause current to lag or lead voltage, creating reactive power that does no useful work but still flows through conductors and transformers. Apparent power (measured in volt-amperes) represents the total power the source must deliver, while real power (watts) is the actual work performed.

Enter any two known values — voltage and current, real power and power factor, or apparent power and power factor — to compute the complete power triangle including all three power components and the phase angle. It gives you a quick check before you choose a transformer or generator size.

When This Page Helps

Use this calculator when you need to size AC equipment from the full power triangle instead of treating watts and amps as interchangeable. It is useful for transformer sizing, generator planning, and checking whether a load will stress a circuit because of poor power factor. That helps you stay within the actual VA limit instead of just the watt rating.

How to Use the Inputs

  1. Select the input mode based on what values you know.
  2. Enter voltage and current for direct apparent power calculation.
  3. Enter or adjust the power factor (0 to 1, where 1 is purely resistive).
  4. For three-phase systems, toggle the three-phase option.
  5. Review the complete power triangle: S (VA), P (W), Q (VAR).
  6. Use presets for common load types to see typical power factors.
  7. Check transformer/generator sizing recommendations.
Formula used
Apparent Power S (VA) = V × I. Real Power P (W) = S × cos(θ) = S × PF. Reactive Power Q (VAR) = S × sin(θ) = S × √(1 - PF²). Power Factor = P / S = cos(θ). Phase Angle θ = arccos(PF). Three-Phase: S = √3 × V_L × I_L.

Example Calculation

Result: S = 4,800 VA, P = 4,080 W, Q = 2,530 VAR

S = 240 × 20 = 4,800 VA. P = 4,800 × 0.85 = 4,080 W. Q = 4,800 × sin(arccos(0.85)) = 4,800 × 0.527 = 2,530 VAR. Phase angle = 31.8°.

Tips & Best Practices

  • Always size transformers and generators in kVA, not kW — the difference matters at low power factors.
  • Power factor correction capacitors should be installed as close to the inductive load as possible.
  • Motors running below 50% load have dramatically worse power factor — right-size your motors.
  • A VFD (variable frequency drive) often improves power factor to 0.95+ at the input.
  • Measure power factor with a clamp meter that reads true power — basic meters only show VA.

The Power Triangle

The power triangle is a right triangle relating the three types of AC power. The hypotenuse is apparent power S (VA), the adjacent side is real power P (W), and the opposite side is reactive power Q (VAR). The angle θ between S and P is the phase angle, and cos(θ) equals the power factor.

When PF = 1, the triangle collapses to a line (S = P, Q = 0). As PF decreases, Q grows and S increases for the same P. At PF = 0.5, the source must deliver twice the apparent power to produce the same real work.

Three-Phase Power

Three-phase systems are standard in commercial and industrial settings. For balanced three-phase loads: S = √3 × V_line × I_line. The √3 factor (≈1.732) appears because three phases share the load. Three-phase power is more efficient for transmission and provides constant instantaneous power delivery, unlike single-phase which pulsates at twice the line frequency.

Power Factor Correction Economics

Utility companies typically charge demand penalties when power factor drops below 0.85-0.90. The cost of capacitor banks pays back in 1-3 years through reduced demand charges, lower I²R losses, and freed-up system capacity. Automatic power factor correction controllers switch capacitor banks on and off to maintain target PF as loads vary throughout the day.

Sources & Methodology

Last updated:

Frequently Asked Questions

  • Watts (W) measure real power — the actual work performed. Volt-amperes (VA) measure apparent power — the total power flowing in the circuit. They differ when power factor is less than 1. VA ≥ W always. For purely resistive loads (PF=1), VA = W.