Cable Size Calculator

Calculate correct electrical cable and wire gauge for any circuit. Account for voltage drop, ampacity, distance, and NEC requirements.

Recommended Wire
AWG 8
Copper — 16,510 cmil
Voltage Drop
4.69V
1.95% (max 3%)
Ampacity
50A
Circuit: 30A
Limiting Factor
Voltage Drop
Long run requires larger wire
Required cmil
10,750
Wire provides 16,510 cmil
Power Loss
≈ 0W
I²R losses in conductor

Voltage Drop

1.95%
Max: 3%

Wire Gauge Comparison

AWGcmilVD (V)VD (%)AmpacityStatus
126,53011.854.9%25A
1010,3807.463.1%35A
816,5104.692.0%50A
626,2402.951.2%65A
441,7401.850.8%85A
352,6201.470.6%100A
NEC Common Circuit Requirements
CircuitAmpsMin Copper AWGMin Al AWG
Lighting15A1412
General Receptacle20A1210
Dryer / Water Heater30A108
Range / Cooktop40-50A6-84-6
EV Charger (Level 2)40-50A6-84-6
100A Subpanel100A31
200A Service200A2/04/0
Planning notes, formulas, and examples

About the Cable Size Calculator

The Cable Size Calculator determines the correct wire gauge (AWG) for electrical circuits based on current, voltage, distance, and allowable voltage drop. Proper wire sizing ensures safety, code compliance, and efficient power delivery.

Undersized wires create fire hazards, trip breakers, and waste energy through excessive resistance heating. Oversized wires waste money on unnecessary copper or aluminum. This calculator finds the optimal gauge by checking both ampacity (current-carrying capacity per NEC Table 310.16) and voltage drop limits (typically 3% for branch circuits, 5% total including feeder).

Enter your circuit parameters — current, voltage, one-way distance, conductor material, and installation conditions — to get the minimum wire size that satisfies both ampacity and voltage drop requirements. It gives you a practical starting point for choosing a safe conductor before you buy the wire. That is especially useful when you are comparing a short run to a long one, or deciding whether a larger gauge is worth it.

When This Page Helps

Use this calculator when you need a wire size that satisfies both ampacity and voltage-drop limits instead of checking only one side of the problem. It is useful for branch circuits, feeders, and longer runs where the code-minimum gauge may not be the performance-minimum gauge. That matters most when distance starts to erode usable voltage at the load.

How to Use the Inputs

  1. Enter the circuit current in amps (or load in watts with voltage).
  2. Select the system voltage (120V, 208V, 240V, 480V, etc.).
  3. Enter one-way wire run distance in feet.
  4. Select conductor material: copper or aluminum.
  5. Set maximum allowable voltage drop percentage.
  6. Review the recommended AWG gauge and supporting calculations.
  7. Check the wire comparison table for alternatives.
Formula used
Wire Size (cmil) = (2 × K × I × D) / VD. Where K = resistivity (copper: 12.9, aluminum: 21.2 Ω·cmil/ft), I = current (A), D = one-way distance (ft), VD = allowable voltage drop (V). Voltage Drop % = VD / System Voltage × 100.

Example Calculation

Result: AWG 8 copper wire

VD allowed = 240 × 0.03 = 7.2V. cmil = 2 × 12.9 × 30 × 100 / 7.2 = 10,750. AWG 10 = 10,380 cmil (too small). AWG 8 = 16,510 cmil (sufficient). AWG 8 ampacity = 40A (>30A). Use 8 AWG.

Tips & Best Practices

  • Always check BOTH ampacity AND voltage drop — the larger wire size wins.
  • For 120V circuits, voltage drop is twice as critical as 240V for the same current and distance.
  • Use 90°C rated wire (THWN-2, XHHW-2) for ampacity but derate to 75°C for terminations.
  • Underground runs in conduit may need additional derating for soil temperature and fill.
  • When in doubt, go one size larger — the cost difference is small compared to a redo.

NEC Ampacity Tables

NEC Table 310.16 provides the foundation for wire sizing. For 75°C-rated copper wire in normal conditions: 14 AWG = 20A, 12 AWG = 25A, 10 AWG = 35A, 8 AWG = 50A, 6 AWG = 65A, 4 AWG = 85A, 3 AWG = 100A, 2 AWG = 115A, 1 AWG = 130A, 1/0 = 150A, 2/0 = 175A, 3/0 = 200A, 4/0 = 230A.

These values assume no more than 3 current-carrying conductors, 30°C ambient temperature, and a single conduit or cable. Derating is required for higher temperatures, more conductors, or bundled cables.

Voltage Drop Calculations

For single-phase circuits: VD = 2 × I × R × D / 1000 (where R is resistance per 1000ft). For three-phase circuits: VD = √3 × I × R × D / 1000. Using circular mils directly: VD = 2 × K × I × D / cmil for single-phase.

The factor of 2 accounts for the round trip (hot and neutral). In three-phase balanced circuits, √3 replaces 2 because neutral current is zero under balanced conditions.

Common Circuit Sizes

15A circuit (typical lighting): 14 AWG copper, up to 50ft. 20A circuit (general receptacles): 12 AWG, up to 50ft. 30A circuit (dryer, water heater): 10 AWG, up to 50ft. 40A circuit (range, large appliance): 8 AWG. 50A circuit (ranges, subpanels): 6 AWG. 100A subpanel: 3 AWG copper or 1 AWG aluminum. 200A service: 2/0 copper or 4/0 aluminum.

Sources & Methodology

Last updated:

Frequently Asked Questions

  • NEC requires minimum 10 AWG copper (or 8 AWG aluminum) for 30-amp circuits. However, voltage drop over long runs may require larger wire. A 30A circuit at 240V running 100ft may need 8 AWG copper for acceptable voltage drop.