Wire Gauge Calculator

Calculate AWG wire gauge, diameter, resistance, ampacity, and voltage drop. Size conductors for electrical circuits with NEC compliance checks.

amps
volts
feet
%
Recommended Gauge
AWG 8
128.5 mil diameter
Voltage Drop
1.9%
2.33V of 120V
Ampacity (75°C)
50A
Load: 20A copper
Resistance
0.778 Ω/kft
Per 1000 feet
Min by Ampacity
AWG 14
Without voltage drop consideration
Total Wire Needed
150 ft
75 ft × 2 conductors

Wire Gauge Comparison

AWG 14
7.9% | 20A
AWG 12
5.0% | 25A
AWG 10
3.1% | 35A
AWG 8
1.9% | 50A
AWG 6
1.2% | 65A
AWG 4
0.8% | 85A
AWG 3
0.6% | 100A
AWG 2
0.5% | 115A

AWG Reference Table (Copper)

AWGDia (mil)Area (CM)Ω/1000ftAmp (75°C)V-DropStatus
1464.14,1103.140207.9%✗ Drop
1280.86,5301.980255.0%✗ Drop
10101.910,3801.240353.1%✗ Drop
8128.516,5100.778501.9%✓ OK
6162.026,2400.491651.2%✓ OK
4204.341,7400.308850.8%✓ OK
3229.452,6200.2451000.6%✓ OK
2257.666,3600.1941150.5%✓ OK
1289.383,6900.1541300.4%✓ OK
1/0324.9105,6000.1221500.3%✓ OK
2/0364.8133,1000.0971750.2%✓ OK
3/0409.6167,8000.0772000.2%✓ OK
4/0460.0211,6000.0612300.2%✓ OK
Planning notes, formulas, and examples

About the Wire Gauge Calculator

Choosing the correct wire gauge prevents overheating, fire hazards, and excessive voltage drop. The Wire Gauge Calculator helps you select the right AWG (American Wire Gauge) size based on current load, circuit length, and allowable voltage drop — following NEC (National Electrical Code) ampacity requirements. It is a practical check against undersizing a run that looks acceptable at first glance.

AWG is the standard wire sizing system in North America, where smaller numbers mean larger wire. AWG 14 (15A residential circuits), AWG 12 (20A circuits), AWG 10 (30A dryer/AC), and AWG 6 (50A range/EV charger) cover most household needs. For industrial and commercial applications, AWG 4/0 through 500 MCM handle heavy loads.

It gives wire diameter, cross-sectional area, resistance per foot, ampacity for different insulation types, and voltage drop for any circuit length. It handles both copper and aluminum conductors, supports single-phase and three-phase calculations, and flags NEC code violations — essential for electricians, engineers, and DIY homeowners.

When This Page Helps

Use this calculator when you need to size conductors for current, distance, and voltage-drop limits instead of guessing from a chart. It is useful for residential runs, equipment feeds, and any circuit where safety and performance both matter. It also helps explain when voltage drop, not ampacity, is what forces a larger conductor.

How to Use the Inputs

  1. Enter the circuit current (amps) and voltage
  2. Enter the one-way wire run distance
  3. Select conductor material (copper or aluminum)
  4. Set the allowable voltage drop percentage (typically 3%)
  5. Review the recommended wire gauge and actual voltage drop
  6. Check the AWG reference table for detailed specifications
Formula used
Wire Diameter: d(in) = 0.005 × 92^((36-AWG)/39). Resistance: R = ρ × L / A (Ω/1000ft from NEC tables). Voltage Drop: Vd = 2 × I × R × L / 1000 (single phase). Ampacity per NEC Table 310.16.

Example Calculation

Result: Recommended: AWG 10 (voltage drop: 2.4%, NEC ampacity: 30A)

A 20A circuit at 120V running 75 feet one-way needs AWG 10 copper wire to keep voltage drop under 3%. AWG 12 has 3.2% drop (over the 3% target). AWG 10 has NEC ampacity of 30A with 75°C insulation, well above the 20A load.

Tips & Best Practices

  • When in doubt, go one size up — the cost difference is small compared to rework
  • Voltage drop matters most for long runs (>50 ft) and sensitive equipment
  • Aluminum wire needs AL-CU rated connectors and anti-oxidant paste at every connection
  • NEC ampacity tables assume 30°C (86°F) ambient — derate for hotter environments
  • Conduit fill affects ampacity — more than 3 current-carrying conductors requires derating
  • For 240V circuits, voltage drop is half that of 120V circuits at the same power and distance

AWG System Explained

The American Wire Gauge system dates to 1857 and is based on the number of drawing dies the wire passes through. Starting from a 0.4600-inch rod (roughly AWG 4/0 or 0000), each die reduces diameter by a fixed ratio (approximately 1.123). After 39 dies, you reach AWG 36 at 0.005 inches.

Key relationships: every 3 gauge steps doubles the cross-sectional area. AWG 10 (10.38 mm²) has twice the area of AWG 13 (5.19 mm²). Every 6 gauge steps doubles the diameter. This geometric progression means AWG 0000 (4/0) is 107.2 mm² while AWG 40 is just 0.0079 mm².

NEC Ampacity Considerations

NEC Table 310.16 lists ampacities for insulated conductors at 30°C ambient with no more than 3 current-carrying conductors. Real installations often need adjustments: more than 3 conductors in a raceway requires derating (Table 310.15(C)(1)). Ambient temperature above 30°C requires further derating. Continuous loads (3+ hours) require the conductor ampacity to be at least 125% of the load current.

For residential wiring, the most common configurations are: 15A circuits on AWG 14, 20A on AWG 12, 30A on AWG 10, 40A on AWG 8, and 50A on AWG 6 (all copper, 60°C termination).

Voltage Drop for Long Runs

Voltage drop becomes the controlling factor for long wire runs. The NEC recommendation of 3% branch circuit drop (5% total) is informational, not mandatory — but essential for proper equipment operation. Motors starting on circuits with high voltage drop may fail to start or overheat. LED drivers may flicker. Electronic equipment may malfunction.

For long runs, calculate voltage drop first, then verify NEC ampacity. The required gauge often needs to be 1-3 sizes larger than the NEC ampacity minimum. For example, a 20A circuit at 120V running 150 feet needs AWG 6 copper to stay under 3% drop, even though AWG 12 would be sufficient by ampacity alone.

Sources & Methodology

Last updated:

Frequently Asked Questions

  • NEC recommends (but doesn't require) max 3% voltage drop for branch circuits and 5% total (feeder + branch). A 120V circuit with 3% drop delivers 116.4V at the load. Excessive drop causes dim lights, motor overheating, and device malfunction. Long runs need larger wire to compensate.